Publication 900-UM004D-EN-E - July 2010
Communications Data for Modbus 5-9
➊ The setting (monitor) range depends on the Transfer Output Type setting. (See the setting data list for details.)
➋ The parameter will not be shown on the Controller display when Alarm 3 is not assigned to an output.
Table 5.8
Address Parameter Name Setting (Monitor) Value Function
Group
Four-byte
mode
Two-byte
mode
0E28 2E14 Transfer Output Upper Limit H'FFFFF831…H'0000270F (−1999…9999) ➊ Initial
Setting
0E2A 2E15 Transfer Output Lower Limit H'FFFFF831…H'0000270F (−1999…9999) ➊
0E48 2E24 Extraction of Square Root
Enable
H'00000000 (0): OFF
H'00000001 (1): ON
0F00 2F00 Alarm 1 Type H'00000000 (0): Alarm function OFF
H'00000001 (1): Upper and lower-limit alarm
H'00000002 (2): Upper-limit alarm
H'00000003 (3): Lower-limit alarm
H'00000004 (4): Upper and lower-limit range alarm
H'00000005 (5): Upper and lower-limit alarm w/ standby sequence
H'00000006 (6): Upper-limit alarm w/ standby sequence
H'00000007 (7): Lower-limit alarm w/ standby sequence
H'00000008 (8): Absolute-value upper-limit alarm
H'00000009 (9): Absolute-value lower-limit alarm
H'0000000A (10): Absolute-value upper-limit alarm w/ standby sequence
H'0000000B (11): Absolute-value lower-limit alarm w/ standby sequence
H'0000000C (12): LBA (Loop Burnout Alarm)
H'0000000D (13): PV change rate alarm
0F02 2F01 Alarm 1 Latch H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
Setting
0F04 2F02 Alarm 1 Hysteresis H'00000001…H'0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)
Initial
Setting
0F06 2F03 Alarm 2 Type H'00000000 (0): Alarm function OFF
H'00000001 (1): Upper and lower-limit alarm
H'00000002 (2): Upper-limit alarm
H'00000003 (3): Lower-limit alarm
H'00000004 (4): Upper and lower-limit range alarm
H'00000005 (5): Upper and lower-limit alarm w/ standby sequence
H'00000006 (6): Upper-limit alarm w/ standby sequence
H'00000007 (7): Lower-limit alarm w/ standby sequence
H'00000008 (8): Absolute-value upper-limit alarm
H'00000009 (9): Absolute-value lower-limit alarm
H'0000000A (10): Absolute-value upper-limit alarm w/standby sequence
H'0000000B (11): Absolute-value lower-limit alarm w/ standby sequence
H'0000000C (12): No alarm function
H'0000000D (13): PV change rate alarm
0F08 2F04 Alarm 2 Latch H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
Setting
0F0A 2F05 Alarm 2 Hysteresis H'00000001…H'0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)
Initial
Setting
0F0C 2F06 Alarm 3 Type ➋ Same settings as the Alarm 2 type.