Publication 900-UM004D-EN-E - July 2010
3-12 Communications Data
C3 (83) 0071 Monitor/Setting Item
4
H’00000000...H’0000000F (0 ...5)
* Same as for Monitor/Setting Item 1.
Advanced
function
settingC3 (83) 0072 Monitor/Setting Item
5
H’00000000...H’0000000F (0 ...5)
* Same as for Monitor/Setting Item 1.
C3 (83) 0073 PV/SP Display Screen
Selection
H’00000000 (0): PV/SP
H’00000001 (1): PV/SP/Multi-SP
PV/SP/MV
H’00000002 (2): PV/SP/MV
PV/SP/Multi-SP
H’00000003 (3): PV/SP/Multi-SP
H’00000004 (4): PV/SP/MV
H’00000005 (5): PV/SP/Multi-SP
PV/SP/Soak Time Remain
H’00000006 (6): PV/SP/MV
PV/SP/Soak Time Remain
H’00000007 (7): PV/SP/Soak Time Remain
C3 (83) 0074 MV Display Screen
Selection
H’00000000 (0): OFF (heating)
H’00000001 (1): ON (cooling)
C3 (83) 0075 PV Decimal Point
Display
H’00000000 (0): OFF
H’00000001 (1): ON
C3 (83) 0076 PV Status Display
Function
H’00000000 (0): OFF
H’00000001 (1): Manual
H’00000002 (2): Stop
H’00000003 (3): Alarm 1
H’00000004 (4): Alarm 2
H’00000005 (5): Alarm 3
H’00000006 (6): Alarm 1 to 3 OR status
H’00000007 (7): Heater alarm
C3 (83) 0077 SV Status Display
Function
H’00000000...H’00000006 (0...7)
* Same as for PV Status Display Function
C3 (83) 0078 Control Output 1
ON/OFF Count Alarm
Set Value
H’00000000...0000270F (0...9999)
C3 (83) 0079 Control Output 2
ON/OFF Count Alarm
Set Value
H’00000000...0000270F (0...9999)
C3 (83) 0083 Display Refresh
Period
H’00000000 (0): OFF
H’00000001 (1): 0.25
H’00000002 (2): 0.5
H’00000003 (3): 1.0
Table 3.3 Variable Type C3 (83)
Variable
Typ e
Address Item (Parameter) Set (Monitor) Value Function
Group
The input type can be selected to march the connected sensor. There are two input types specifications:
Thermocouple/Resistance thermometer input and Analog input.
The parameter will not be shown on the Controller display when alarm 3 is not assigned to an output.
Communications parameters are enabled after they have been changed by resetting the controller.
For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 1
or 2
For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 2.
PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.
The logic of CompoWay/F (900-TC) operation command code 00 (communications writing) is not affected.
The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)
P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.
The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.