Publication 900-UM004D-EN-E - July 2010
Communications Data 3-3
C1 (81) 0003 Set Point SP lower limit to SP upper limit Operating
C1 (81) 0004 Alarm Value 1 H’FFFFF831…H’0000270F (-1999…9999)
C1 (81) 0005 Upper-Limit Alarm 1 H’FFFFF831…H’0000270F (-1999…9999)
C1 (81) 0006 Lower-Limit Alarm 1 H’FFFFF831…H’0000270F (-1999…9999)
C1 (81) 0007 Alarm Value 2 H’FFFFF831…H’0000270F (-1999…9999)
C1 (81) 0008 Upper-Limit Alarm 2 H’FFFFF831…H’0000270F (-1999…9999)
C1 (81) 0009 Lower-Limit Alarm 2 H’FFFFF831…H’0000270F (-1999…9999)
C1 (81) OOOA Alarm Value 3 ➊ H’FFFFF831…H’0000270F (-1999…9999)
C1 (81) OOOB Upper-Limit
Alarm 3 ➊
H’FFFFF831…H’0000270F (-1999…9999)
C1 (81) OOOC Lower-Limit
Alarm 3 ➊
H’FFFFF831…H’0000270F (-1999…9999)
C1 (81) 000D Heater burnout
detection 1
H’00000000…H’000001 F4 (0.0…50.0) Adjust
-ment
C1 (81) 000E SP 0 SP lower limit…SP upper limit
C1 (81) 000F SP 1 SP lower limit…SP upper limit
C1 (81) 0010 SP 2 SP lower limit…SP upper limit
C1 (81) 0011 SP 3 SP lower limit…SP upper limit
C1 (81) 0012 Temperature input
shift
H’FFFFF831…H’0000270F (-199.9…999.9)
C1 (81) 0013 Upper-limit
temperature input
shift value
H’FFFFF831…H’0000270F (-199.9…999.9)
C1 (81) 0014 Lower-limit
temperature input
shift value
H’FFFFF831…H’0000270F (-199.9…999.9)
C1 (81) 0015 Proportional band H’00000001…H’0000270F (0.1…999.9)
C1 (81) 0016 Integral time H’00000000…H’00000F9F (0…3999)
C1 (81) 0017 Derivative time H’00000000…H’00000F9F (0…3999) (Range when RT is “OFF”)
H’00000000…H’0000270F (0…999.9) (Range when RT is “ON”)
C1 (81) 0018 Cooling coefficient H’00000001…H’0000270F (0.01…99.99)
C1 (81) 0019 Dead band H’FFFFF831…H’0000270F
(-199.9…999.9 for TC/Pt universal input models)
(-19.99...99.99 for analog input models)
C1 (81) 001A Manual reset value H’00000000…H’000003E8 (0.0…100.0)
C1 (81) 001B Hysteresis (Heating) H’00000001…H’0000270F
(0.1…999.9 for TC/Pt universal input models)
(.01...99.99 for analog input models)
C1 (81) 001C Hysteresis (Cooling) H’00000001…H’0000270F
(0.1…999.9 for TC/Pt universal input models)
(.01...99.99 for analog input models)
C1 (81) 001D Heater burnout 2
detection
H’00000000…H’000001F4 (0.0…50.0)
C1 (81) 001E HS alarm 1 H’00000000…H’000001F4 (0.0…50.0)
C1 (81) 001F HS alarm 2 H’00000000…H’000001F4 (0.0…50.0)
C1 (81) 0020 Soak time H’00000001…H’0000270F (1…9999)
C1 (81) 0021 Wait band H’00000000 (0): OFF
H’00000001…H’0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)
C1 (81) 0022 MV at stop Standard: H’FFFFFFCE…H’0000041A (−5.0…105.0)
Heating and cooling: H’FFFFFBE6…H’0000041A (−105.0…105.0)
C1 (81) 0023 MV at PV error Standard: H’FFFFFFCE…H’0000041A (−5.0…105.0)
Heating and cooling: H’FFFFFBE6…H’0000041A (−105.0…105.0)
C1 (81) 0024 Manual manipulated
variable
Standard: H’FFFFFFCE…H’0000041A (−5.0…105.0)
Heating and cooling: H’FFFFFBE6…H’0000041A (−105.0…105.0)
Manual
Control
Table 3.2 Variable Type C1 (81)
Variable
Typ e
Address Item (Parameter) Set (Monitor) Value Function
Group