Publication 900-UM004D-EN-E - July 2010
Communications Data for Modbus 5-7
Table 5.6
Address Parameter Name Setting (Monitor) Value Function Group
Four-byte mode Two-byte mode
0D06 2D03 Linear Current Output H'00000000 (0): 4…20 mA
H'00000001 (1): 0…20 mA
Initial Setting function
group
0D1E 2C0F SP Upper Limit The range of values (without decimal point) is as
follows:
Temperature: SP lower limit + 1…Input range
upper limit
Analog: SP lower limit + 1…scaling upper limit
0D20 2D10 SP Lower Limit The range of values (without decimal point) is as
follows:
Temperature: Input range lower limit…SP upper
limit − 1
Analog: Scaling lower limit…SP upper limit − 1
0D22 2D11 Standard or Heating
and Cooling
H'00000000 (0): Standard
H'00000001 (1): Heating and cooling
0D24 2D12 Direct/Reverse
Operation
H'00000000 (0): Reverse operation
H'00000001 (1): Direct operation
0D28 2D14 PID/OnOff H'00000000 (0): ON/OFF
H'00000001 (1): 2 degrees of freedom PID control
0D2A 2D15 ST H'00000000 (0): OFF
H'00000001 (1): ON
0D2C 2D16 Program Pattern H'00000000 (0): OFF
H'00000001 (1): STOP
H'00000002 (2): CONT
0E00 2E00 Transfer Output Type H'00000000 (0): OFF
H'00000001 (1): Set point
H'00000002 (2): Set point during SP ramp
H'00000003 (3): PV
H'00000004 (4): MV monitor (heating)
H'00000005 (5): MV monitor (cooling)
Kommentare zu diesen Handbüchern