Publication 900-UM004D-EN-E - July 2010
Communications Data 3-5
Table 3.3 Variable Type C3 (83)
Variable
Typ e
Address Item (Parameter) Set (Monitor) Value Function
Group
C3 (83) 0000 Input Type (TC/Pt
multi-input models)
➊
H’00000000 (0): Pt (−200…850°C/−300…1500°F)
H’00000001 (1): Pt (−199.9…500.0°C/−199.9…900.0°F)
H’00000002 (2): Pt (0.0…100.0°C/0.0…210.0°F)
H’00000003 (3): JPt (−199.9…500.0°C/−199.9…900.0°F)
H’00000004 (4): JPt (0.0…100.0°C/0.0…210.0°F)
H’00000005 (5): K (−200…1300°C/−300…2300°F)
H’00000006 (6): K (−20.0…500.0°C/0.0…900.0°F)
H’00000007 (7): J (−100…850°C/−100…1500°F)
H’00000008 (8): J (−20.0…400.0°C/0.0…750.0°F)
H’00000009 (9): T (−200…400°C/−300…700°F)
H’0000000A (10): T (−199.9…400.0°C/−199.9…700.0°F)
H’0000000B (11): E (0…600°C/0…1100°F)
H’0000000C (12): L (−100…850°C/−100…1500°F)
H’0000000D (13): U (−200…400°C/−300…700°F)
H’0000000E (14): U (−199.9…400.0°C/−199.9…700.0°F)
H’0000000F (15): N (−200…1300°C/
−300…2300°F)
H’00000010 (16): R (0…1700°C/0…3000°F)
H’00000011 (17): S (0…1700°C/0…3000°F)
H’00000012 (18): B (100…1800°C/300…3200°F)
H’00000013 (19): Infrared temperature sensor (K 140°F/60°C)
H’00000014 (20):Infrared temperature sensor (K 240°F/120°C)
H’00000015 (21):Infrared temperature sensor (K 280°F/140°C)
H’00000016 (22): Infrared temperature sensor (K 440°F/220°C)
H’00000017 (23): 0…50 mV
H’00000018 (24): W (0... 2300°C/0...3200°F)
H’00000019 (25): PL II (0... 1300°C/0...2300°F)
Initial
setting
Input Type (analog
input models) ➊
H’00000000 (0): 4…20 mA
H’00000001 (1): 0…20 mA
H’00000002 (2): 1…5 V
H’00000003 (3): 0…5 V
H’00000004 (4): 0…10 V
C3 (83) 0001 Scaling Upper Limit Scaling lower limit +1…0000270F (scaling lower limit +1…9999)
C3 (83) 0002 Scaling Lower Limit H’FFFFF831 to Scaling upper limit -1 (-1999 to scaling upper limit
-1)
C3 (83) 0003 Decimal Point
Position (TC/Pt
multi-input models)
H’00000000…H’00000001 (0…1)
Decimal Point
Position (analog input
models)
H’00000000…H’00000003 (0…3)
C3 (83) 0004 Temperature Unit H’00000000(0): °C
H’00000001(1): °F
C3 (83) 0005 SP Upper Limit The range of values (without decimal point) is as follows:
Temperature: SP lower limit + 1 to Input range upper limit
Analog: SP lower limit + 1 to Scaling upper limit
C3 (83) 0006 SP Lower Limit The range of values (without decimal point) is as follows:
Temperature: Input range lower limit to SP upper limit - 1
Analog: Scaling lower limit to SP upper limit - 1
C3 (83) 0007 PID/ ON/OFF H’00000000(0) ON/OFF
H’00000001(1) 2-PID Control
C3 (83) 0008 Standard/Heating
and Cooling
H’00000000(0): Standard
H’00000001 (1) Heating and cooling
➊ The input type can be selected to march the connected sensor. There are two input types specifications:
Thermocouple/Resistance thermometer input and Analog input.
➋ The parameter will not be shown on the Controller display when alarm 3 is not assigned to an output.
➌ Communications parameters are enabled after they have been changed by resetting the controller.
➍ For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 1
or 2
➎ For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 2.
➏ PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.
➐ The logic of CompoWay/F (900-TC) operation command code 00 (communications writing) is not affected.
➑ The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)
➒ P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.
➓ The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.