Publication 900-UM004D-EN-E - July 2010
Communications Data 3-11
C3 (83) 0054 Soak time unit H’00000000 (0): Minutes
H’00000001 (1): Hours
Advanced
function
setting
C3 (83) 0055 Alarm SP selection H’00000000 (0): Set point during SP ramp
H’00000001 (1): Set point
C3 (83) 0056 Auxiliary Output 3
assignment
H’00000000…H’0000000F (0…15)
* Same settings as Auxiliary Output 1 assignments
C3 (83) 005B Manual MV limit
enable
H’00000000 (0): OFF
H’00000001 (1): ON
C3 (83) 005D AT calculated gain H’00000001...H’00000064 (0.1...10.0)
C3 (83) 005E AT Hysteresis H’00000001...0000270F (0.1...999.9: Controllers with TC/Pt
universal input)
(0.01...9.99: Controllers with analog input)
C3 (83) 005F Limit Cycle MV
amplitude
H’00000032...H’000001F4 (5.0...50.0)
C3 (83) 0067 PV Rate of change
calculation period
H’00000001...H’000003E7 (1...999)
C3 (83) 0068 Automatic Cooling
coefficient
adjustment
H’00000000 (0): OFF
H’00000001 (1): ON
C3 (83) 0069 Heater Overcurrent
use
H’00000000 (0): OFF
H’00000001 (1): ON
C3 (83) 006A Heater Overcurrent
latch
H’00000000 (0): OFF
H’00000001 (1): ON
C3 (83) 006B Heater Overcurrent
Hysteresis
H’00000001...H’000001F4 (0.1...50.0)
C3 (83) 006C Extraction of square
root enable
H’00000000 (0): OFF
H’00000001 (1): ON
Initial set-
ting
C3 (83) 006D PF Setting H’00000000 (0): Not assigned.
H’00000001 (1): Run
H’00000002 (2): Stop
H’00000003 (3): RUN/STOP
H’00000004 (4): 100% AT execute
H’00000005 (5): 40% AT execute
H’00000006 (6): Alarm latch cancel
H’00000007 (7): Auto/manual switch
H’00000008 (8): Monitor/setting item
Advanced
function
setting
C3 (83) 006E Monitor/Setting Item
1
H’00000000 (0): Disabled
H’00000001 (1): PV/SP/Multi-SP
H’00000002 (2): PV/SP/MV
H’00000003 (3): PV/SP/soak time remain
H’00000004 (4): Proportional band (P)
H’00000005 (5): Integral time (I)
H’00000006 (6): Derivative time (D)
H’00000007 (7): Alarm value 1
H’00000008 (8): Alarm value upper limit 1
H’00000009 (9): Alarm value lower limit 1
H’0000000A (10): Alarm value 2
H’0000000B (11): Alarm value upper limit 2
H’0000000C (12): Alarm value lower limit 2
H’0000000D (13): Alarm value 3
H’0000000E (14): Alarm value upper limit 3
H’0000000F (15): Alarm value lower limit 3
C3 (83) 006F Monitor/Setting Item
2
H’00000000...H’0000000F (0 ...5)
* Same as for Monitor/Setting Item 1.
C3 (83) 0070 Monitor/Setting Item
3
H’00000000...H’0000000F (0 ...5)
* Same as for Monitor/Setting Item 1.
Table 3.3 Variable Type C3 (83)
Variable
Typ e
Address Item (Parameter) Set (Monitor) Value Function
Group
➊ The input type can be selected to march the connected sensor. There are two input types specifications:
Thermocouple/Resistance thermometer input and Analog input.
➋ The parameter will not be shown on the Controller display when alarm 3 is not assigned to an output.
➌ Communications parameters are enabled after they have been changed by resetting the controller.
➍ For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 1
or 2
➎ For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 2.
➏ PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.
➐ The logic of CompoWay/F (900-TC) operation command code 00 (communications writing) is not affected.
➑ The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)
➒ P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.
➓ The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.