3-10 Communications Data
C3 (83) 004E Control output 1
assignment
When control output 1 is a linear output:
H’00000000 (0): Not assigned.
H’00000001 (1): Control output (heating)
H’00000002 (2): Control output (cooling)
When control output 1 is an ON/OFF pulse output:
H’00000000 (0): Not assigned.
H’00000001 (1): Control output (heating)
H’00000002 (2): Control output (cooling)
H’00000003 (3): Alarm 1
H’00000004 (4): Alarm 2
H’00000005 (5): Alarm 3
H’00000006 (6): Program end output
H’00000007 (7): Control output ON/OFF count alarm
Advanced
function
setting
C3 (83) 004F Control output 2
assignment
H’00000000 (0): Not assigned.
H’00000001 (1): Control output (heating)
H’00000002 (2): Control output (cooling)
H’00000003 (3): Alarm 1
H’00000004 (4): Alarm 2
H’00000005 (5): Alarm 3
H’00000006 (6): Program end output)
H’00000007 (7): Control output ON/OFF count alarm
C3 (83) 0050 Auxiliary Output 1
assignment
H’00000000 (0): Not assigned.
H’00000001 (1): Control output (heating)
H’00000002 (2): Control output (cooling)
H’00000003 (3): Alarm 1
H’00000004 (4): Alarm 2
H’00000005 (5): Alarm 3
H’00000006 (6): Program end output)
H’00000007 (7): Control output ON/OFF count alarm
C3 (83) 0051 Auxiliary Output 2
assignment
H’00000000…H’0000000F (0…15)
* Same settings as Auxiliary Output 1 assignments
C3 (83) 0052 Character select H’00000000 (0): OFF
H’00000001 (1): ON
C3 (83) 0053 Program pattern H’00000000 (0): OFF
H’00000001 (1): STOP
H’00000002 (2): CONT
Initial
setting
Table 3.3 Variable Type C3 (83)
Variable
Typ e
Address Item (Parameter) Set (Monitor) Value Function
Group
The input type can be selected to march the connected sensor. There are two input types specifications:
Thermocouple/Resistance thermometer input and Analog input.
The parameter will not be shown on the Controller display when alarm 3 is not assigned to an output.
Communications parameters are enabled after they have been changed by resetting the controller.
For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 1
or 2
For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 2.
PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.
The logic of CompoWay/F (900-TC) operation command code 00 (communications writing) is not affected.
The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)
P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.
The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.