Publication 900-UM004D-EN-E - July 2010
Communications Data for Modbus 5-5
Table 5.4
The alarm function can also be used in Controllers without alarm output terminals. In this case, confirm alarm
occurrences via the status data.
Address Parameter Name Setting (Monitor) Value Function
Group
Four-byte
mode
Two-byte
mode
0750 2728 Soak Time Remain Monitor H’00000000…H’0000270F (0…9999) Operating
0752 2729 Soak Time H’00000001…H’0000270F (1…9999) Adjustment
0754 272A Wait Band H’00000000 (0): OFF
H’00000001…H’0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)
0756 272B Heater Overcurrent Detection 1 H’00000000…H’000001F4 (0.0…50.0)
0758 272C Heater Overcurrent Detection 2 H’00000000…H’000001F4 (0.0…50.0)
0800 2800 Input Digital Filter H’00000000…H’0000270F (0.0…999.9) Advanced
Setting
0810 2808 Extraction of Square Root Low-cut Point H’00000000…H’000003E8 (0.0…100.0) Adjustment
0900 2900 Set Point 0 SP lower limit…SP upper limit
0904 2902 Alarm Value 1 H’FFFFF831…H’0000270F (1999…9999) Operating
0906 2903 Upper-Limit Alarm 1 H’FFFFF831…H’0000270F (1999…9999)
0908 2904 Lower-Limit Alarm 1 H’FFFFF831…H’0000270F (1999…9999)
090A 2905 Alarm Value 2 H’FFFFF831…H’0000270F (1999…9999)
090C 2906 Upper-Limit Alarm 2 H’FFFFF831…H’0000270F (1999…9999)
090E 2907 Lower-Limit Alarm 2 H’FFFFF831…H’0000270F (1999…9999)
0910 2908 Alarm Value 3 H’FFFFF831…H’0000270F (1999…9999)
0912 2909 Upper-Limit Alarm Value 3 H’FFFFF831…H’0000270F (1999…9999)
0914 290A Lower-Limit Alarm Value 3 H’FFFFF831…H’0000270F (1999…9999)
091C 290E SP 1 SP lower limit to SP upper limit Adjustment
0938 291C SP 2 SP lower limit to SP upper limit
0954 292A SP 3 SP lower limit to SP upper limit
0A00 2A00 Proportional Band H’FFFFF831…H’0000270F (1999…9999)
0A02 0A01 Integral Time H’00000000…H’00000F9F (0.0…3999
0A04 2A02 Derivative Time H'00000000 to H'00000F9F (0 to 3999) (Range when RT
is “OFF.”)
H'00000000 to H'0000270F (0.0 to 999.9) (Range when
RT is “ON.”)
0A0A 2A05 MV Upper Limit Standard: MV lower limit + 0.1 to H’0000041A (MV
lower limit + 0.1 to 105.0)
Heating and cooling: H'00000000 to H'0000041A (0.0 to
105.0)
0A0C 2A06 MV Lower Limit Standard: H’FFFFFFCE to MV upper limit - 0.1 (-5.0 to MV
upper limit - 0.1)
Heating and cooling: H'FFFFFBE6 to H'00000000 (-105.0
to 0.0
Seitenansicht 86