Rockwell-automation AADvance Controller Configuration Guide Bedienungsanleitung Seite 90

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 286
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 89
4-50
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
RTC Status: Seconds
Direction: input to application from controller
Type: word
Values:
0 to 59
Description:
Reports the oldest value of real-time clock (RTC) seconds as voted by every 9110
processor module which is present and synchronized. Only updated if the real-time
clock control Boolean RTC Read is set to TRUE. If RTC Read is FALSE, the value will
be 0 (zero).
RTC Status: Milliseconds
Direction: input to application from controller
Type: word
Values:
0 to 999
Description:
Reports the oldest value of real-time clock (RTC) milliseconds as voted by every 9110
processor module which is present and synchronized. Only updated if the real-time
clock control Boolean RTC Read is set to TRUE. If RTC Read is FALSE, the value will
be 0 (zero).
RTC Program Variables
The variables in the rack of RTC program variables specify parts of the date to be
written to the real-time clock the next time the RTC control variable RTC Write is
asserted TRUE.
Note: The values will be written only if the RTC control variable Year is TRUE.
Seitenansicht 89
1 2 ... 85 86 87 88 89 90 91 92 93 94 95 ... 285 286

Kommentare zu diesen Handbüchern

Keine Kommentare