Document: 553633
ICSTT-RM405f-EN-P
Issue 07
The default values disable the statistics reporting.
3) Set the Reporting Mode.
4) Set the Data Variable Address to the Modbus address of the relevant holding
register.
5) Similarly set the Reset Variable Address.
6) Click Apply.
Modbus Statistics Parameters
Each Modbus message has a series of parameters as detailed in the table.
Table 36: Modbus Slave Link Message Parameters
Disabled;
Last Rate;
Maximum Rate:
Average Rate
Sets the application statistic to
report
1 to 65,536,
or 0 to disable
Data variable is reported in
hundredths of a second
1 to 65,536,
or 0 to disable
Write any non-zero value to the
reset variable to reset the data
variable to zero
Remove a Slave Link
You can remove an unwanted slave link. Do the following:
1) Select the Equipment tab on the Project tree view and locate the unwanted
Modbus slave link.
2) Right-click on the slave link and select Remove Slave.
The slave link is deleted.