Rockwell-automation AADvance Controller Configuration Guide Bedienungsanleitung Seite 113

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 286
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 112
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
5-15
<tagname>.XRUN
BOOL
Run status
Reports the run status of module X
TRUE: the module is on-line and reporting
channel values, or requires manual
intervention (pressing the Fault Reset button)
before values can be reported, otherwise
FALSE
<tagname>.XSDN
BOOL
Shutdown status
Reports that module X requires manual
intervention (pressing the Fault Reset button)
before values can be reported
TRUE: the module needs manual intervention
<tagname>.XPOS
INT
Position
Reports the slot number of module X (1 to
24) (†)
Note: (†) Slots are numbered 1 to 24 on both buses; the slot location (.LOC) and
position (XPOS) do not identify the bus.
Seitenansicht 112
1 2 ... 108 109 110 111 112 113 114 115 116 117 118 ... 285 286

Kommentare zu diesen Handbüchern

Keine Kommentare