Restart a Slave with Ping disabled
1) Configure the salve with a Control Variable Address.
This is the address of the Modbus holding register for the slave link control
variable.
2) Set the Slave control register variable to a 0 (off)
3) Set the control register variable to 2 (active)
The master will restart communication with the slave.
Restart All Active Slaves Associated with a Master
1) Select the Master object.
2) Set a Control Variable Address
This is the address of the Modbus holding register for the control variable.
3) Set the Master Control Variable to 0 (off)
4) Set the Master Control Variable to 2 (active).