Parameters for CIP Producer and Consumer Varaibles
Each production variable and consumption variable for CIP over Ethernet/IP
communications has a set of parameters as detailed in the tables.
Note: A maximum of 128 producer and 128 consumer variables can be defined.
Table 18: Parameters for Production Variables
Maximum number
of connections
The maximum number of simultaneous
consumers of the particular variable (†)
Note: (†) The AADvance controller rejects any CIP requests to connect to a
produced variable beyond the maximum number of connections (255). Do not set the
number of connections higher than necessary because each connection uses resources
from a limited pool.
Table 19: Parameters for Consumption Variables
A unique string
Can include spaces and
other punctuation
characters
A user-defined name for the producing device
labelled 'Device Name' in Producer List.
A valid address for a
Logix controller
Labelled 'CIP Path to Device' in Producer List.
(refer to Configure an AADvance Variable as a
consumer)
Specifies the name of the variable as it is known
to the Logix controller.
Requested packet interval
Defines how frequently the Logix controller
should offer the variable to the AADvance
controller.
Note: (‡) The RPI should not be set below 200ms at the current release.