Rockwell-automation AADvance Controller Configuration Guide Bedienungsanleitung Seite 134

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 286
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 133
5-36
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
Configuration Procedure
1) In the Dictionary create the following variables.
2) Create a variable which will be used to enable/disable control in the application,
this variable must be BOOL type with its direction set to output.
3) Create variables for each Analogue Input/Output channel connected to a HART
Field Device that the AMS is required to communicate with, this variable must be
the T9K_AI_HART_FULL type with its direction set as input.
4) In the Equipment View
5) Select the 9110 Processor Module and the Variables tab on the 9110 Module
Editor.
Seitenansicht 133
1 2 ... 129 130 131 132 133 134 135 136 137 138 139 ... 285 286

Kommentare zu diesen Handbüchern