208 Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
Chapter 9 Diagnostics
Table 30 - Fault Indication
Fault Definitions
Short Circuit
Short Circuit indicates that the Bulletin 140M motor protector has tripped, or
that the internal wiring protection algorithm has detected an unsafe current
surge. This fault cannot be disabled.
Overload Trip
The load has drawn excessive current and based on the overload trip class
selected, the device has tripped. This fault cannot be disabled.
Phase Loss
Indicates a missing supply phase. This fault can be disabled and is disabled by
default.
Blink Pattern
Fault Types
Bulletin 280E/281E Bulletin 284E
1 Short Circuit Short Circuit
2 Overload Trip Overload Trip
3 Phase Loss Phase Short
4 Reserved Ground Fault
5 Reserved Stall
6 Control Power Control Power
7 I/O Fault I/O Fault
8 Over Temperature Over Temperature
9 Phase Imbalance Over Current
10 A3 Power Loss A3 Power Loss
11 Reserved Internal Communications
12 Reserved DC Bus Fault
13 EEPROM Fault EEPROM Fault
14 Hardware Fault Hardware Fault
15 Reserved Restart Retries
16 Reserved Misc. Fault