
124 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Bit
Function
131211109876543210
————————————— X Short Circuit
———————————— X — Overload
——————————— X —— Phase Loss
—————————— X ——— Reserved
————————— X ———— Reserved
———————— X ————— Control Power
——————— X —————— I/O Fault
—————— X ——————— Over Temperature
————— X ———————— Phase Imbalance
———— X ————————— A3 Power Loss
——— X —————————— Reserved
—— X ——————————— Reserved
— X ———————————— EEprom
X ————————————— HW Fault
Pr Fault Reset
This parameter resets the Protection
Fault on a transition of
0 > 1.
Parameter Number 25
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Str Net FltState
This parameter in conjunction with
Parameter 27 (Str Net FltValue)
defines how the starter will respond
when a fault occurs as determined by
Parameter 27. Allows Starter to hold
last state or go to FltValue on
NetFaults.
0 = Goto Fault Value
1 = Hold Last State
Parameter Number 26
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Kommentare zu diesen Handbüchern