Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 159
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Output Power
The output power present at T1, T2,
and T3.
Parameter Number 122
Access Rule GET
Data Type UINT
Group
Drive Display
Units
Minimum Value 0.00
Maximum Value Drive rated power X 2
Default Value Read Only
Output Power Fctr
The angle in electrical degrees
between motor voltage and current.
Parameter Number 123
Access Rule GET
Data Type UINT
Group Drive Display
Units 0.1°
Minimum Value 0.0°
Maximum Value 180.0°
Default Value Read Only
Drive Temp
Present operating temperature of the
drive power section.
Parameter Number 124
Access Rule GET
Data Type UINT
Group Drive Display
Units 1 °C
Minimum Value 0
Maximum Value 120
Default Value Read Only
Counter Status
The current value of the counter when
counter is enabled.
Parameter Number 125
Access Rule GET
Data Type UINT
Group Drive Display
Units 1
Minimum Value 0
Maximum Value 9999
Default Value Read Only