200 Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
215 Process Time Lo
Scales the time value when the drive is running at Parameter 134
(Minimum Freq). When set to a value other than zero, Parameter
110 (Process Display) indicates the duration of the process.
0.00 Drive Advanced Setup
216 Process Time Hi
Scales the time value when the drive is running at Parameter 135
(Maximum Freq). When set to a value other than zero, Parameter
110 (Process Display) indicates the duration of the process.
0.00 Drive Advanced Setup
217 Bus Reg Mode
Enables the bus regulator.
1 = Enabled Drive Advanced Setup
218 Current Limit 2
Maximum output current allowed before current limiting occurs.
Drive Rated
Amps x 1.5
Drive Advanced Setup
219 Skip Frequency
Sets the frequency at which the drive will not operate.
0.0 Hz Drive Advanced Setup
220 Skip Freq Band
Determines the brand width around Parameter 219 (Skip
Frequency). Parameter 220 (Skip Freq Band) is split applying 1/2
above and 1/2 below the actual skip frequency.
0.0 Hz Drive Advanced Setup
221 Stall Fault Time
Sets for the fault time that the drive will remain in stall mode
before a fault is issued.
0 = 60 Seconds Drive Advanced Setup
222 Option not valid for Bulletin 284E ArmorStart.
223 Option not valid for Bulletin 284E ArmorStart.
224 Var PWM Disable
Enables/disables a feature that varies the carrier frequency for
the PWM output waveform defined by Parameter 191 (PWM
Frequency).
0 = Enabled Drive Advanced Setup
225 Torque Perf Mode
Enables/disables sensorless vector control operation.
1 = Sensrls Vect Drive Advanced Setup
226 Motor NP FLA
Set to the motor nameplate full load amps.
Drive Rated Amps Drive Advanced Setup
227 Autotune
Provides an automatic method for setting Parameter 228
(IR Voltage Drop) and Parameter 229 (Flux Current Ref), which
affect sensorless vector performance.
0 = Ready/Idle Drive Advanced Setup
228 IR Voltage Drop
Value of volts dropped across the resistance of the motor stator.
Based on Drive
Rating
Drive Advanced Setup
229 Flux Current Ref
Value of amps for full motor flux.
Based on Drive
Rating
Drive Advanced Setup
230 PID Trim Hi
Sets the maximum positive value that is added to a PID reference
when PID trim is used.
60.0 Drive Advanced Setup
231 PID Trim Lo
Sets the minimum positive value that is added to a PID reference
when PID trim is used.
0.1 Drive Advanced Setup
232 PID Ref Sel
Enables/disables PID mode and selects the source of the PID
reference.
0 = PID Disabled Drive Advanced Setup
233 PID Feedback Sel
Valid PID Feedback Sel command for the Bulletin 284E
ArmorStart.
0 = 0-10V Input Drive Advanced Setup
234 PID Prop Gain
Sets the value for the PID proportional component when the PID
mode is enabled by Parameter 232 (PID Ref Sel).
0.01 Drive Advanced Setup
235 PID Integ Time
Sets the value for the PID integral component when the PID mode
is enabled by Parameter 232 (PID Ref Sel).
0.1 Secs Drive Advanced Setup
236 PID Diff Rate
Sets the value for the PID differential component when the PID
mode is enabled by Parameter 232 (PID Rel Sel).
0.01 (1/Secs) Drive Advanced Setup
Table 29 - Parameter Descriptions
Parameter
Number
Parameter
Name
Description Factory Default Group