10–9Diagnostic Status Information
Publication
17706.5.16 - October 1996
Bytes Bits Contents Description
1771KG Module (Series B)
1 0 = second module; 1 = first module
2 0 = accept physical/unprotected reads and writes disabled
1 = accept physical/unprotected reads and writes enabled
4, 3, 0 Binary values:
Value Parity Error Embedded Protocol
Check Responses
000 none BCC disabled fullduplex
100 even BCC disabled fullduplex
010 none BCC enabled fullduplex
110 even BCC enabled fullduplex
001 none BCC disabled halfduple
x
101 even BCC disabled halfduple
x
011 none CRC enabled fullduplex
111 none CRC disabled halfduple
x
5 - 7 Asynchronous link baud rate:
0 = 110 bps 1 = 300 bps 2 = 600 bps
3 = 1200 bps 4 = 2400 bps 5 = 4800 bps
6 = 9600 bps 7 = 19200 bps