9–25Diagnostic Counters
Publication
17706.5.16 - October 1996
Cat. Nos. Link Pages
1784KR DH485 9-3
1784KT, KT2 DH+ 9-25
1784KT and 1784KT2 DH+ Diagnostic Counters
This counter byte Counts the number of
0 Times received ACKs with a bad CRC.
1 Timeouts expired with no ACK received.
2 Transmit retries exhausted.
3 NAK or illegal protocol operations received.
4 NAKs - bad LSAP received.
5 NAK - no memory received.
6 Received ACKs/NAKs that were too short.
7 Received ACKs/NAKs that were too long.
8 Times something other than an ACK/NAK received.
9 Duplicate tokens found.
10 Token pass timeouts.
11 Token pass retries exhausted.
12 Claim token sequence entered.
13 Tokens claimed.
14 Bad CRC in received frame.
15 NAKs sent - illegal protocol operation.
16 NAK sent - bad LSAP.
17 NAK sent - no memory.
18 Received frames that were too short.
19 Received frames that were too long.
20 Retransmissions received of a frame.
21 Received frames aborted (line noise).
22, 23 Messages successfully sent (low byte first).
24, 25 Messages successfully received (low byte first).
26, 27 Commands successfully sent (low byte first).
28, 29 Replies successfully received (low byte first).
30, 31 Commands successfully received (low byte first).
32, 33 Replies successfully sent (low byte first).
34 Replies that could not be sent (low byte first).
35 Number of active nodes.
1784 Cat. Nos.