9–27Diagnostic Counters
Publication
17706.5.16 - October 1996
1785KA DH+ Diagnostic Counters
This counter byte Counts the number of
0 Times received ACKs with a bad CRC.
1 Timeouts expired with no ACK received.
2 Transmit retries exhausted.
3 NAK/illegal protocol operations received.
4 NAK/bad LSAP received.
5 NAK/no memory received.
6 Received ACKs/NAKs too short.
7 Received ACKs/NAKs too long.
8 Times something other than an ACK/NAK received.
9 Duplicate tokens found.
10 Duplicate nodes found.
11 Token pass timeouts.
12 Token pass retries exhausted.
13 Claim token sequences entered.
14 Tokens claimed.
15 Bad CRC in received frames.
16 NAKs - illegal protocol operations sent.
17 NAKs - bad LSAP sent.
18 NAKs - no memory sent.
19 Received frames that were too small.
20 Received frames that were too long.
21 Frame retransmissions received.
22 Received frames aborted (line noise).
23, 24 Messages successfully sent (low byte first).
25, 26 Messages successfully received (low byte first).
27, 28 Commands successfully sent (low byte first).
29, 30 Replies successfully received (low byte first).
31, 32 Commands successfully received (low byte first).
33, 34 Replies successfully sent (low byte first).
35 Replies that could not be sent.
36 Active nodes.