7–26 Communication Commands
Publication
17706.5.16 - October 1996
set CPU mode
Sets the operating mode of the processor at the next I/O scan.
The operating mode is set to the mode indicated in the flag byte
(shown below). A “no privilege” error is returned if the requester
does not have the privilege of placing the host in Download mode.
This error occurs when:
the processor is not in Remote mode (must be in Remote Program
mode, Remote Run mode, or Remote Test mode)
the processor is being edited
some other node is already downloading to the processor
CMD
0F
STS
FNC
3A
TNS
C
CMD
4F
STS
TNS
R
DST SRC
SRC DST
EXT
STS
The
EXT STS field may be attached to the reply packet only when there is an error
.
A
76543 2 10
00000 0 10
unused
determine which operating mode is selected
or
, for some products, remote lock
For this operating mode A is
Program/Load (processor idle, I/O disabled) 00000000
Remote Test (processor scanning, I/O disabled) 00000001
Remote Run (processor scanning, I/O enabled) 00000010
No change (only remote bit affected) 00000011
PLC5