11-50
SP600 AC Drive User Manual
Sets the reaction to a loss of input power. Power loss is recognized
when:
DC bus voltage is ≤ 73% of DC Bus Memory and Power Loss Mode
is set to Coast.
DC bus voltage is ≤ 82% of DC Bus Memory and Power Loss Mode
is set to Decel.
Sets the time that the drive will remain in power loss mode before a
fault is issued.
Sets the level at which the Power Loss Mode (184) selection will
occur.
184 Power Loss Mode
Range: 0 = Coast
1 = Decel
2 = Continue
3 = Coast input
4 = Decel input
Default: 0 = Coast
Access: 1 Path: Dynamic Control>Stop/Power Loss
See also: 184
185 Power Loss Time
Range: 0.0 to 60.0 Sec [0.1 Sec]
Default: 0.5 Sec
Access: 1 Path: Dynamic Control>Stop/Power Loss
See also: 184
186 Power Loss Level
Range: 0.0 to 999.9 V [0.1 V]
Default: 0.0 V
Access: 2 Path: Dynamic Control>Power Loss
See also: 184