Rockwell-automation SP600 User Manual Version 3.0 Bedienungsanleitung Seite 148

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 274
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 147
11-46
SP600 AC Drive User Manual
Issuing a stop command from any control source. (Note that
removal of a 2-wire run-fwd or run-rev command is considered a
stop command.)
Issuing a fault reset command from any active source.
Removing the enable input signal.
Setting Auto Restrt Tries to zero.
Occurrence of a fault that is not auto-resettable.
Removing power from the drive.
Exhausting an auto-reset/run cycle.
Sets the time between restart attempts when the auto restart
feature is enabled. Refer to Auto Rstrt Tries (174) for more
information about the auto restart feature.
Enables the Sleep-Wake function.
175 Auto Rstrt Delay
Range: 0.5 to 30.0 Sec [0.1 Sec]
Default: 1.0 Sec
Access: 1 Path: Dynamic Control>Stop/Restart Modes
See also: 174
178 Sleep-Wake Mode
Range: 0 = Disabled
1 = Direct
Default: 0 = Disabled
Access: 2 Path: Dynamic Control>Restart Modes
See also:
!
ATTENTION: Enabling the Sleep-Wake function
can cause unexpected machine motion during the
Wake mode. Do not use this function without
considering the information in the table below.
Failure to observe this precaution could result in
personal injury or damage to equipment.
Seitenansicht 147
1 2 ... 143 144 145 146 147 148 149 150 151 152 153 ... 273 274

Kommentare zu diesen Handbüchern

Keine Kommentare