Publication 1760-UM002B-EN-P - March 2005
2-26 Installation
Set Point Potentiometer
Figure 2.27 Set Point potentiometer, set point potentiometer with upstream resistor
Use a potentiometer with a resistance of greater than or equal to1 k, e.g. 1 k,
0.25W.
Temperature Sensor, Brightness Sensor, 20 mA Sensor
Figure 2.28 Temperature sensor, brightness sensor, 20 mA sensor
4 to 20 mA (0 to 20 mA) sensors can be connected using an external 500
resistor.
The following values apply:
4 mA = 1.9V
10 mA = 4.8V
20 mA = 9.5V
(according to U = R x I = 478 x 10 mA ~ 4.8V)