Publication 1760-UM002B-EN-P - March 2005
4-146 Wiring with Pico GFX-70
Figure 4.68 Signal diagram of timing relay, off-delayed
(with/without random switching with/without retriggering)
1: trigger coil T..EN
2: stop coil T..ST
3: reset coil T..RE
4: switching contact (make contact) T..Q1
t
s
: setpoint time
Range A:
The time elapses after the trigger coil is deactivated.
Range B:
The Stop coil stops the time from elapsing.
Range C:
The Reset coil resets the relay and the contact. After the Reset coil drops out, the relay
continues to work normally.
Range D:
The Reset coil resets the relay and the contact when the function block is timing out.