AN-T80004
Issue 10 Jun 13 AN-T80004 1
Application Note
Field Loop Configuration
The Trusted
TM
Input/Output (I/O) modules are designed to monitor field loops for alarm and field cable
fault states. The configuration of field loops differs between modules.
This application note:
explains the circuits required to allow line monitoring of field wiring.
describes connection and configuration options for different device types, including system and
field powered types, volt-free, current sourcing and sinking and two, three and four wire
devices.
suggests options for isolation and protection.
Issue Record
Issue
Number
Date Modification
1 Feb 07 Initial Issue
2 Aug 07 T8297 connections
3 Dec 07 Circuit options
4 Feb 08 Comments incorporated
5 Jun 08 De-en LM Outputs
6 Sep 08 System cable design
7 Dec 08 Low current loads
8 Feb 10 2,3,4 wire AI,8472 nlthresh
9 Aug 12 Clarifications to DI line monitoring
10 Jun 13 T8403 states 0 and 6 not used
Seitenansicht 0
1 2 3 4 5 6 ... 55 56

Inhaltsverzeichnis

Seite 1 - Application Note

TrustedTM AN-T80004 Issue 10 Jun 13 AN-T80004 1 Application Note Field Loop Configuration The TrustedTM Input/Output (I/O) modules ar

Seite 2 - Table of Contents

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 10 T8433 Termination Options The T8433 TrustedTM Isolated Analogue Input mo

Seite 3

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 11 The T8834 FTA is a configurable version of the T8433. This also connects

Seite 4

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 12 For field powered devices, sourcing current, where the channel current c

Seite 5 - Analogue Inputs

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 13 Configuration There are seven input voltage state thresholds dete

Seite 6

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 14 Threshold online update The channel thresholds can be read or written us

Seite 7

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 15 Overvoltage Faults The analogue inputs are not designed to measure volta

Seite 8

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 16 Digital Inputs Thresholds Digital inputs are essentially analogue inputs

Seite 9 - Millivolt inputs

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 17 Line Monitoring and Marshalling for Volt-Free Inputs Field loops provi

Seite 10 - T8433 Termination Options

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 18 T8403 TMR Inputs When using the TrustedTM TMR 24V dc Digital Input Modul

Seite 11

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 19 For systems conforming to AANSI/ISA non-incendive hazardous area

Seite 12

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 2 Table of Contents Analogue Inputs ...

Seite 13 - Configuration

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 20 T8424 120V ac Digital Input The T8424 is actually a T8431 analogue input

Seite 14 - Threshold online update

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 21 Non volt-free digital inputs The information above is for isolated volt-

Seite 15 - Overvoltage Faults

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 22 Field powered inputs These inputs appear as a voltage signal, powered

Seite 16 - Digital Inputs

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 23 Hall Effect and Open Collector/Open Drain These devices are all essentia

Seite 17 - T8402 Dual Inputs

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 24 Zone Interface and Valve Monitor Inputs The T8448 and T8449 modules have

Seite 18 - T8403 TMR Inputs

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 25 Configuration T8448 and T8449 inputs may be monitored by the ap

Seite 19

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 26 Frequency/Pulse Inputs The T8442 Speed Monitor Module is designed to mon

Seite 20 - T8424 120V ac Digital Input

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 27 Digital Outputs Power Groups Digital Output module channels are arranged

Seite 21 - Non volt-free digital inputs

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 28 Line Monitoring Outputs do not have threshold templates. Instead, the st

Seite 22 - Field powered inputs

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 29 Output energised/on (state 4) This occurs when the channel output curren

Seite 23

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 3 Short circuit in field wiring or load (state 5) ...

Seite 24 - Diagnostic Test Termination

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 30 No-load (Open Circuit) Threshold Triplicated Modules 8448, 8449, 8451, 8

Seite 25

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 31 It is advised to add load resistors to loads under about 20

Seite 26 - Frequency/Pulse Inputs

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 32 Termination Powered digital output terminations are very simple, with mi

Seite 27 - Digital Outputs

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 33 V_FIELD_GRP1V_FIELD_RTN_GRP1FIELDTERMINALSV_FIELD_RTN_GRP1 ( SK1 AND 2

Seite 28 - Line Monitoring

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 34 ‘Standard’ cables have two short tails on the chassis end. These cables

Seite 29 - Channel fault (state 7+)

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 35 Terminating Resistors Unused outputs should be commanded off/de-ene

Seite 30

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 36 If the relay load current is less than the minimum, an extra load resist

Seite 31

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 37 Caution Devices that cannot be reliably line monitored when de-energised

Seite 32 - Termination

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 38 Analogue Outputs The Trusted T8480 Analogue Output module may be conside

Seite 33 - T8850 and T8870 FTAs

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 39 Output energised (state 4) This state occurs with a load fitted w

Seite 34 - T8472 Termination

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 4 Floating Earth Systems and Loop Isolation ...

Seite 35 - Volt-free outputs

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 40 Pulse Outputs Applications have occasionally required pulse-width modula

Seite 36 - Device Characteristics

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 41 IO Real -100% to +100% Pulse width from continuous off demand

Seite 37 - Power supply fluctuations

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 42 The pulse width bias factor is used when the valve moves faster in one d

Seite 38 - Analogue Outputs

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 43 Other Issues System Cable Design The diagrams below show how to wi

Seite 39

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 44 Analogue or Digital Input module to VFTA The T8842 VFTA has five power

Seite 40 - Pulse Outputs

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 45 Digital Output module to FTA, Standard Cable The ‘standard’ output c

Seite 41

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 46 Digital Output module to FTA, integral power cable The ‘integral powe

Seite 42

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 47 Digital Output module to VFTA The TC-209, TC-509, TC-210 and TC-510

Seite 43 - Other Issues

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 48 Analogue Outputs Analogue output circuit options are the same as the di

Seite 44

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 49 Floating Earth Systems and Loop Isolation ICS Triplex Technology rec

Seite 45

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 5 Analogue Inputs Line monitoring Field loops providing analogue input

Seite 46

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 50 potentials applied serially across components. Where lightning strikes a

Seite 47

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 51 Cable earth and screen wires At either end of an I/O cable there may be

Seite 48

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 52 Free Wire Cables I/O cables without FTA or VFTA plugs are availa

Seite 49 - Non-incendive certification

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 53 TC-206/506/208/508 (40 Channel Output) These cables have a short connect

Seite 50 - HART interfacing

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 54 TC-216/516/218/518 (40 Channel Output with Integral Power) Power wires T

Seite 51 - Cable earth and screen wires

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 55 TC-602/702/604/704 (60 Channel Input) These cables are idented CH0

Seite 53

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 6 The T8842 Versatile Field Termination Assembly (VFTA) provides i

Seite 54

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 7 This circuit cannot be used. Usually the current loop is not even returne

Seite 55

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 8 The current loop allows 4mA to drive the device electronics. However, mo

Seite 56

TrustedTM AN-T80004 Field Loop Configuration Issue 10 Jun 13 AN-T80004 9 Millivolt inputs The T8840 allows a block of eight channels of a T8431 to