3-42
SB3000 Drive Configuration and Programming
Parallel Power Module B Status Register (Continued) 220/1220
Phase W-Lower IOC B Bit 5
The Phase W-Lower B status bit is set if an
IOC or DSAT fault occurs in Power Module
B’s phase W, lower power device.
Hex Value: 0020H
Sug. Var. Name: W_LOB@
Access: Read only
UDC Error Code: N/A
LED: N/A
Intelligent Power Module B Bit 6
The Intelligent Power Module B bit is set to
indicate that a DSAT (shoot-through) fault
has occurred in Power Module B.
Hex Value: 0040H
Sug. Var. Name: IPUB@
Access: Read only
UDC Error Code: N/A
LED: N/A
Bits 0 - 5 of this register should be checked to identify the device in which the fault
occurred.
GDI Fault B Bit 7
The GDI Fault B bit is set if a fault is
detected in the power supply of Power
Module B’s Gate Driver Interface module.
Hex Value: 0080H
Sug. Var. Name: GDIB@
Access: Read only
UDC Error Code: N/A
LED: N/A
Charge Fault B Bit 8
The Charge Fault B bit is set if a charge bus
time-out fault occurs in Power Module B
(refer also to register 202/1202, bit 6).
Hex Value: 0100H
Sug. Var. Name: CHGB@
Access: Read only
UDC Error Code: N/A
LED: N/A
Over Temperature B Bit 12
The Over Temperature B bit is set if an over
temperature fault or warning occurs in
Power Module B.
Hex Value: 1000H
Sug. Var. Name: OTB@
Access: Read only
UDC Error Code: N/A
LED: N/A