Configuring the UDC Module’s Registers
3-7
Table 3.3 – Rail I/O Port Registers
Drive A
Registers
Drive B
Registers Port and Channel
Rail Type and Signal
4 Output
1
4 Input
2
2 Input
3
2 Output
Digital
I/O
4
0 12 Port 0 - Channel 0 Output 0 Input 0 Output 0 Digital
1 13 Port 0 - Channel 1 Output 1 Input 1 Output 1 N/A
2 14 Port 0 - Channel 2 Output 2 Input 2 Input 2 N/A
3 15 Port 0 - Channel 3 Output 3 Input 3 Input 3 N/A
4 16 Port 0 - Fault Register (Tables 3.4 - 3.6)
5 17 Port 0 - Check Bit Fault Count Register (Tables 3.4 - 3.6)
6 18 Port 1 - Channel 0 Output 0 Input 0 Output 0 Digital
7 19 Port 1 - Channel 1 Output 1 Input 1 Output 1 N/A
8 20 Port 1 - Channel 2 Output 2 Input 2 Input 2 N/A
9 21 Port 1 - Channel 3 Output 3 Input 3 Input 3 N/A
10 22 Port 1 - Fault Register (Tables 3.4 - 3.6)
11 23 Port 1 - Check Bit Fault Count Register (Tables 3.4 - 3.6)
1. 4-Output Analog Rail Module (M/N 61C365, 61C366)
2. 4-Input Analog Rail Module (M/N 61C345, 61C346)
3. 2-Output/2-Input Analog Rail Module (M/N 61C350, 61C351)
4. Digital I/O Rail (M/N 45C1), Thumbwheel Switch Input Module (M/N 45C630), or LED Output Module (M/N 45C631
Table 3.4 – Fault Register and Check Bit Fault Counter Register
Usage for a Digital I/O Rail or 4-Output Analog Rail Module
Drive A
Registers
Drive B
Registers Description
4 16 Port 0 Fault Register
10 22 Port 1 Fault Register
Bit 8: No device plugged into a configured port
Bit 9: Bad ID code: device other than a rail plugged into the
port
Bit 10: Bad rail communication check bits received
Bit 11: PMI interface is not ready
5 17 Port 0 Check Bit Fault Counter Register
11 23 Port 1 Check Bit Fault Counter Register
These registers can be reset by setting bit 9 of the Drive
Control register (100/1100)