C-14
EtherNet/IP Communications Module
N-Files
N-File Description
N40 This N-file lets you use Emulated Block Transfer messages to read and write
many types of DPI messages. To use Emulated Block Transfer messages, you
send a Write message to N40:0 – N40:63, wait until the module responds with a
reply message, and then read the response data in N40:0 – N40:63 with a Read
message.
Bits 15 to 8 are the Most Significant Byte. Bits 7 to 0 are the Least Significant
Byte.
Write Read
Bits 15 0 15 0
N40:0 0x00 Length (in Bytes) 0x00 Length (in Bytes)
N40:1 DPI Port 0x81 Status Size Status Type
N40:2 0x00 CIP Services Data
(length varies based on message)
N40:3 CIP Class
N40:4 CIP Instance
N40:5 CIP Attribute
N40:6 Data
(length varies based on message)
N40:63
N41 This N-file lets you read and write control I/O messages. You can write control I/O
messages only when all of the following conditions are true:
The module is not receiving I/O from a scanner. For example, there is no
scanner on the network, the scanner is in idle (program) mode, the scanner
is faulted, or the module is not mapped to the scanner.
The module is not receiving Peer I/O from another module.
The module is configured to receive I/O (for example, the DPI I/O Cfg
parameter).
The value of N42:3 is set to a non-zero value.
Write Read