Rockwell-automation RECOMM-ENET EtherNet/IP Communications Module Bedienungsanleitung Seite 123

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 194
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 122
Module Parameters
B-5
Displays the actual network data rate and duplex mode used by the
module.
Displays the size of the Reference/Feedback. The drive determines
the size of the Reference/Feedback.
Displays the size of each Datalink word. The drive determines the
size of Datalinks.
17 EN Rate Act
Range: 0 = No Link
1 = 10 Mbps Full
2 = 10 Mbps Half
3 = 100 Mbps Full
4 = 100 Mbps Half
Default: 0 = No Link
Type: Read Only
Reset Required: N/A
18 Ref/Fdbk Size
Range: 0 = 16-bit
1 = 32-bit
Default: 0 = 16-bit
Type: Read Only
Reset Required: N/A
19 Datalink Size
Range: 0 = 16-bit
1 = 32-bit
Default: 0 = 16-bit
Type: Read Only
Reset Required: N/A
Seitenansicht 122
1 2 ... 118 119 120 121 122 123 124 125 126 127 128 ... 193 194

Kommentare zu diesen Handbüchern

Keine Kommentare