B-8
EtherNet/IP Communications Module
Displays the I/O that the module is actively transmitting. The value
of this parameter will usually be equal to the value of DPI I/O Cfg
(23).
Sets the Logic Command data that is sent to the drive if the
following is true:
Comm Flt Action (21) is set to Send Flt Cfg and communications
are disrupted.
Idle Flt Action (22) is set to Send Flt Cfg and the scanner is put
into Program or Test mode.
Peer Flt Action (41) is set to Send Flt Cfg and communications
are disrupted.
Important: The bit definitions will depend on the product to which
the module is connected. If the drive uses a 16-bit
Reference, the most significant word of this value must
be set to zero (0) or a fault will occur.
24 DPI I/O Active
Range: See figure B.2.
Default: xxx0 0001
Type: Read Only
Reset Required: N/A
Figure B.2 – DPI I/O Active (24)
00010xxx
01234567
1 = I/O Enabled
0 = I/O Disabled
x =Not Used
Cmd/Ref
Datalink A
Datalink B
Datalink C
Datalink D
Not Used
Not Used
Not Used
25 Flt Cfg Logic
Range: 0000 0000 0000 0000 to 1111 1111 1111 1111
Default: 0000 0000 0000 0000
Type: Read/Write
Reset Required: No