Rockwell-automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Bedienungsanleitung Seite 52

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 168
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 51
5-6
DeviceNet Adapter for use with DPI AC Drives
5.3 Mapping the Drive Data in the
Scanner
Data from I/O messages must be mapped in the scanner. This
mapping determines where a ladder logic program can find data
that is passed over the network. You must map both the Input I/O
and the Output I/O.
5.3.1 Mapping the Input I/O
Step 1. In the Scanner Module dialog box, click the
Input
tab. See
figure 5.5. (If necessary, right-click the scanner in the
configuration view (figure 5.2) to display this dialog box.)
If you selected the
Automap on Add
box in the Scanlist page
(figure 5.3), RSNetWorx has already mapped the I/O. If it is not
mapped, click
Automap
to map it. If you need to change the
mapping, click
Advanced
and change the settings. Click
Help
for
assistance.
Step 2. In the Memory box, select a location in scanner memory
from table 5.4.
Figure 5.5 – Input Page on the Scanner Module Dialog Box
Seitenansicht 51
1 2 ... 47 48 49 50 51 52 53 54 55 56 57 ... 167 168

Kommentare zu diesen Handbüchern

Keine Kommentare