Manage tasks Chapter 1
3. Do one of these steps to inhibit or uninhibit the task.
If You Want to Then
Let the task run when its trigger occurs
Clear Inhibit Task (default).
Prevent the task from running when its trigger
occurs
Check Inhibit Task.
4. Click OK.
Programmatically inhibit or uninhibit a task
To write logic to inhibit or uninhibit a task, use a Set System Value (SSV)
instruction to access the attribute of the Task object for the task.
Attribute Data Type Instruction Description
InhibitTask
DINT
GSV
SSV
Prevents the task from running.
To Set the attribute to
Enable the task 0 (default)
Inhibit (disable) the task 1 (or any non-zero value)