Publication GMLC-5.2 - November 1999
Using Block Transfers 717
In the previous table, the number of decimal digits is shown as a decimal
number. For example, if three decimal digits are specified in the BTW
data file (word 2 = 03xx hex) and the value of the item to be sent to the
motion controller is 1572, the value 1,572,000 (1572 x 1000) must be
stored in the data file. Specifically, since 1,572,000 decimal is 17FCA0
hex, 0017 is stored in the lower numbered word of the word pair (the most
significant word), and FCA0 in the higher numbered word (the least
significant word).
RIO Adapter Block Transfer Write
32-bit Integer Numeric Format
Number of
Decimal
Digits: Multiply PLC Values by:
Maximum Representable Value in the
Motion Controller:
0
1
2
3
4
5
1
10
100
1,000
10,000
100,000
±2,147,483,647.0
±214,748,364.7
±21,474,836.47
±2,147,483.647
±214,748.364 7
±21,474.836 47
6
7
8
9
10
1,000,000
10,000,000
100,000,000
1,000,000,000
10,000,000,000
±2,147.483 647
±214.748 364 7
±21.474 836 47
±2.147 483 647
±0.214 748 364 7
11
12
13
14
15
100,000,000,000
1,000,000,000,000
10,000,000,000,000
100,000,000,000,000
1,000,000,000,000,000
±0.021 474 836 47
±0.002 147 483 647
±0.000 214 748 364 7
±0.000 021 474 836 47
±0.000 002 147 483 647