Rockwell-automation 20-COMM-E PowerFlex EtherNet/IP Adapter Bedienungsanleitung Seite 39

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 296
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 38
Configuring the Adapter 3-11
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
Setting the Adapter to Receive Peer-to-Peer Data
1. Verify that Parameter 47 - [Peer Inp Enable] is set to ‘0’ (Off).
This parameter must be Off while you configure the peer input
parameters.
2. Set Parameters 42 - [Peer Inp Addr 1] through 45 - [Peer Inp Addr
4] to the IP address of the node from which you want to receive data.
Valid nodes must have 20-COMM-E adapters connected to drives with
compatible Logic Command/Status words.
3. Set Parameter 38 - [Peer A Input] to select the destination of the data
that is input to the drive as Peer A.
With the Series A adapter, revision 2.xxx or earlier, if you select a
Reference or Datalink as an input, note the following:
If a drive that uses a 32-bit Reference and 32-bit Datalinks receives a
16-bit Reference or Datalink, it uses the data in its most significant
word, and its least significant word is zero.
If a drive that uses a 16-bit Reference and 16-bit Datalinks receives a
32-bit Reference or Datalink, it uses the data in the most significant
word of the 32-bit Reference or Datalink and ignores the data in the
least significant word.
With the Series B adapter, revision 3.xxx and later, data is used from the
least significant word in the event of a mismatch in Reference or
Datalink sizes.
Value Setting
0 Off (Default)
1On
Port 5 Device
20-COMM-E
Parameter #: 47
Peer Inp Enable
0
Off
Port 5 Device
20-COMM-E
Parameter #: 42
Peer Inp Addr 1
0
0 <> 255
Default = 0.0.0.0
255.255.255.255
[Peer Inp Addr 1]
[Peer Inp Addr 2]
[Peer Inp Addr 3]
[Peer Inp Addr 4]
IP Address of Node
Transmitting Peer I/O
Port 5 Device
20-COMM-E
Parameter #: 38
Peer A Input
1
Cmd/Ref
Value Description
0 Off (Default)
1 Logic Command/Reference
2…5 Datalink A, B, C, or D Input
Seitenansicht 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 295 296

Kommentare zu diesen Handbüchern

Keine Kommentare