Adapter Parameters B-5
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
36 [M-S Output]
Sets the Master-Slave output data. This data is
produced by the adapter and consumed by the
Master device (for example, scanner).
Default: xxx0 0001
Bit Values: 0 = I/O disabled
1 = I/O enabled
Type: Read/Write
Reset Required: Yes
37 [Ref Adjust]
Sets the percent scale factor for the Reference
received from the network.
Default: 100.00%
Minimum: 0.00%
Maximum: 200.00%
Type: Read/Write
Reset Required: No
38
39
[Peer A Input]
[Peer B Input]
Sets the destination of the peer I/O input. The
adapter receives this data from the network and
sends it to the drive.
Important: Changes to these parameters are
ignored when Parameter 47 - [Peer Inp Enable] is
set to ‘1’ (On).
Important: If the parameter is set to input a Logic
Command, configure the mask in Parameter 40 -
[Peer Cmd Mask] so that the desired bits from the
peer device are used.
Default: 0 = Off
Default: 0 = Off
Values: 0 = Off
1 = Cmd/Ref
2 = Datalink A Input
3 = Datalink B Input
4 = Datalink C Input
5 = Datalink D Input
Type: Read/Write
Reset Required: No
40 [Peer Cmd Mask]
Sets the mask for the Logic Command word when
it is received through peer input. If the mask bit is
‘0’ (Off), the command bit is ignored and not used.
If the mask bit is ‘1’ (On), the command bit is
checked and used.
Important: If the adapter receives a Logic
Command from both a Master device and a peer
device, each command bit must have only one
source. The source of command bits set to ‘0’ will
be the Master device. The source of command bits
set to ‘1’ will be the peer device.
Default: 0000 0000 0000 0000
Minimum: 0000 0000 0000 0000
Maximum: 1111 1111 1111 1111
Values: 0 = Ignore bit
1 = Check bit
Type: Read/Write
Reset Required: Yes
Parameter
No. Name and Description Details
Bit
Definition
Not Used
Not Used
Not Used
Datalink D Output
Datalink C Output
Datalink B Output
Datalink A Output
Cmd/Ref
Default xxx00001
Bit 76543210
!
ATTENTION: To guard against equipment damage and/or personal injury, note
that changes to Parameter 37 - [Ref Adjust] take effect immediately. A drive
receiving its Reference from the adapter will receive the newly scaled
Reference, resulting in a change of speed.