Rockwell Automation Publication 193-UM011A-EN-P - September 2010 86
Chapter
7
Diagnostic Parameters
Introduction
This chapter provides an overview of the diagnostic and status parameters
reported by the EC4 Current Monitoring Relay.
Monitor Group
TRIP STATUS
This parameter provides trip identification.
1 = Trip
0 = No Trip
Parameter Number 14
Access Rule Get
Data Type WORD
Object Mapping 0x29-1-114
Group Monitor
Units —
Minimum Value —
Maximum Value —
Default Value None
Bits Function:
1514131211109876543210
X Ground Fault
X L1 Undercurrent
X L2 Undercurrent
X L3 Undercurrent
X L1 Overcurrent
X L2 Overcurrent
X L3 Overcurrent
X L1 Loss
X L2 Loss
X L3 Loss
X Comm Fault
X Comm Idle
X Hardware Fault
XTest Trip
X Remote Trip
XNonVol Mem Fault