Rockwell Automation Publication 193-UM011A-EN-P - September 2010 121
Specifications Appendix A
Electromagnetic
Compatibility
Specifications
➊Performance Criteria 1 requires the DUT to experience no degradation or loss of performance.
➋Environment 2.
Functionality
Specifications
Protection
Table 7 - Electromagnetic Compatibility Specifications
Electrostatic Discharge Immunity
Test Level:
Performance Criteria:
8kV Air Discharge
6kV Contact Discharge
1 ➊➋
RF Immunity
Test Level:
Performance Criteria:
10V/m
1 ➊➋
Electrical Fast Transient/Burst Immunity
Test Level:
Performance Criteria:
4kV (Power)
2kV (Control & Comm)
1 ➊➋
Surge Immunity
Test Level:
Performance Criteria:
2kV (L-E)
1kV (L-L)
1 ➊➋
Radiated Emissions Class A
Conducted Emissions Class A
Table 8 - DeviceNet Communications
Baud Rate 125 k, 250 k, 500 k
Auto-Baud Rate Identification Yes
“Group 2 – Slave Only” device type Yes
Polled I/O Messaging Yes
Change of State Messaging Yes
Cyclic Messaging Yes
Explicit Messaging Yes
Full Parameter Object Support Yes
Group 4 – Off-Line Node Recovery Messaging Yes
Configuring Consistency Value Yes
Unconnected Messaging Manager (UCMM) Yes
Table 9 - Protection
Trip Warning
Undercurrent Yes Yes
Overcurrent Yes Yes
Line Loss Yes Yes