Rockwell-automation 193-EC4 EC4 Current Monitoring Relay User Manual Bedienungsanleitung Seite 127

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 157
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 126
128 Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Appendix B DeviceNet Information
The following tables indicate the I/O Assembly Data Attribute mapping for
Parameter Link-Based Assemblies:
Table 28 - Assembly Object Instance 107 Data Format (“STATUS”)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit3 Bit 2 Bit 1 Bit 0
0 Input4 Input3 Input2 Input1 OutB_Stat
OutA_Stat
Warning Faulted
Table 29 - Assembly Object Instance 141 Data Format (“DEVICELOGIX STAT”)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit3 Bit 2 Bit 1 Bit 0
0 Input4 Input3 Input2 Input1 OutB_Stat
OutA_Stat
Warning Faulted
1Network
Output 7
Network
Output 6
Network
Output 5
Network
Output 4
Network
Output 3
Network
Output 2
Network
Output 1
Network
Output 0
2 DeviceLog
ix Enabled
Network
Output
14
Network
Output 13
Network
Output 12
Network
Output 11
Network
Output 10
Network
Output 9
Network
Output 8
Table 30 - Assembly Object Instance 184 Data Format (“PNB STATUS”)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit3 Bit 2 Bit 1 Bit 0
0Network
Output 7
Network
Output 6
Network
Output 5
Network
Output 4
Network
Output 3
Network
Output 2
Network
Output 1
Network
Output 0
1 DeviceLogi
x Enabled
Network
Output
14
Network
Output 13
Network
Output 12
Network
Output 11
Network
Output 10
Network
Output 9
Network
Output 8
Table 31 - Assembly Object Instance 100 Attributes (“PARAMETER BASED”)
Byte Word Value
0 0 Value of parameter pointed to by param #61 (Low Byte)
1 Value of parameter pointed to by param #61 (High Byte)
2 1 Value of parameter pointed to by param #62 (Low Byte)
3 Value of parameter pointed to by param #62 (High Byte)
4 2 Value of parameter pointed to by param #63 (Low Byte)
5 Value of parameter pointed to by param #63 (High Byte)
6 3 Value of parameter pointed to by param #64 (Low Byte)
7 Value of parameter pointed to by param #64 (High Byte)
Table 32 - Instance 110 Data Link Output Assembly Attributes
(“PARAM LINK CMD”)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit3 Bit 2 Bit 1 Bit 0
0 Remote
Trip
Fault
Reset
Output B Output A
1Reserved
Seitenansicht 126