Publication 1797-6.5.3 - March 2006
F-4 FLEX Ex HART Modules Network Messaging
Handle replaces Preamble. Handle is a number you supply so that the module
returns the Handle with the associated response from the HART command.
The response from the HART command is reformatted to add this handle and
to add additional status information.
Figure F.4 Response from the HART Command
The six header bytes are added in the front of the HART message response
while the remaining format is unchanged. These six bytes contain the
following information:
Response Source
Next Assembly
Pointer to assembly for next access.
Channel
Status
(6 Bytes)
Pass
Through
Handle
Start
Character
Address Command Byte Count (Response
Code)
Data Checksum
Byte 0 123 4 5
Bit02370707070345670127
Resp
Source
Next assy index Ch Handle Resp
Error
Assy
Access
Error
Chain
Data
Req
allow
Loop
status
avail
Lock Cold
Start
Res
Value Meaning
0 Not valid (default)
1 Source is HART response
2 Source is Scan data
3 CMD 48 response
4…7 Reserved