Rockwell-automation 1797-OE8H FLEX Ex HART Analog Modules User Manual Bedienungsanleitung Seite 146

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 196
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 145
Publication 1797-6.5.3 - March 2006
B-22 FLEX Ex HART Module Commands
Command 154
Command 154 is the Rebuild Up to 8 Specified Loops command.
Table B.25 Command 154 Request and Response Data Bytes
Byte Description Value
Request Data Bytes
0 CH_NUM_0 Channel number 0
1 COUNT_0 Number of bytes before next item
CH_NUM_i Channel number i
COUNT_i Number of bytes before next item
Response Data Bytes
0 CH_NUM_0 Channel number 0
1 COUNT_0 Number of bytes before next item
2 ERROR_0 Error 0 0 = Channel
number invalid
64 = Invalid
channel number
CH_NUM_i Channel number i
COUNT_i Number of bytes before next item
ERROR_i Error i
……
Command-specific Response Codes
5 Error Too few data bytes received
16 Error Access restricted
17 Error Too many items requested
32 Error Busy
Seitenansicht 145
1 2 ... 141 142 143 144 145 146 147 148 149 150 151 ... 195 196

Kommentare zu diesen Handbüchern

Keine Kommentare