Publication 1797-6.5.3 - March 2006
FLEX Ex HART Module Commands B-23
Command 158
The Read Special Loop SCAN Parameters command returns the transmitter
data for the given loop, if available. These include:
Loop number
Error flag (0 = ok, 1 = special SCAN not active)
Polling address (always 0, no multidrop)
Selected SCAN command
Long frame address
Number of available data bytes
Data bytes themselves (if any)
Table B.26 Command 158 Request and Response Data Bytes
Byte Description Value
Request Data Bytes
0 CH_NUM Channel number 0…7
Response Data Bytes
0 CH_NUM Channel number 0…7
1 ERROR Error 0 = Special scan
set up for the
selected channel
1 = Special scan
not set up (reply
is truncated to
2bytes)
2 SHORT_ADDR Short address used
3 THRESH Threshold data length for special scan 0…62
4 SCAN_CMD Scan command being used
5…9 EXT_ADDR Extended address of instrument
10 LENGTH Length of data bytes available > 0 if data
available
11… DATA Special scan data (if any)
Command-specific Response Codes
2 Error Invalid selection
5 Error Too few data bytes received
16 Error Access restricted
32 Error Busy
Seitenansicht 146