FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 39
Publication
1797-5.5 - September 2011
Specification 1797-IE8 and -IE8NF (Continued)
Agency Certification
CENELEC
U, C-UL
FM
INMETRO
IECEx
II (1) 2G Ex ib[ia] IIC T4
II (1) D [Ex iaD]
Class I, Groups A, B, C and D; Class II, Groups E, F and
G; Class III hazardous Locations.
Class I, Zone 1, AEx ib[ia] IIC T4.
Intrinsically safe Class I, Div 1, Groups A, B, C, D, T4.
Associated Apparatus with intrinsically safe
Connections Class I, II, III, Div 1, Groups A--G
Intrinsically safe Class I, Zone 1, AEx ib[ia] IIC T4.
BR-Ex ia/ib IIB/IIC T4
[Zone 0] Ex ib[ia] IIC T4
[Ex iaD]
Certificates
CENELEC DMT 98 ATEX E 020 X
UL, C-UL File No.: E197983
FM FM Certificate Number 3009806
INMETRO
IECEX
05/UL-BRAE-0013X (1797-IE8 only)
IECEx BVS 09.0030X
Specifications - 1797-IE8H
Number of Inputs 8 single-ended, non-isolated
IS Input type Ex ia IIB/IIC T4
AEx ia IIC T4
Class I, Division I Groups A-G T4 (FM only)
IS Module type Ex ib IIB/IIC T4
AEx ib IIC T4
Class I, Division I Groups A-D T4 (FM only)
Resolution 16 bits
Transfer Characteristics
Accuracy at 20 °C (68 °F)
Temperature Drift
0.1% of output signal range
0.05%/C of output signal range
Class I Division 1 Hazardous
FM