22 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Publication
1797-5.5 - September 2011
Fault Mode - Write Words 0 and 1
Word 0 Bit 00 Fault enable for Channels 0...3
Word 1 Bit 00 Fault enable for Channels 4...7
Where: O = disable
1 = enable with wire-off overload
“Add-on” Filter Selections - Write Words 0 and 1 or
Filter Cutoff Selections
Word Bits Description
0 07 06 05 Channels 0...3
1 07 06 05 Channels 4...7
000Hardware filtering only (default filtering)
001
40 Hz (25 ms)
01020 Hz (50 ms)
01110 Hz (100 ms)
1004 Hz (250 ms)
1012 Hz (500 ms)
1101 Hz (1 s)
1110.5 Hz (2 s)
Remote Transmitter Error Up/Down - Write Words 0 and 1
Word 0 Bit 08 Up/down for Channels 0...3
Word 1 Bit 08 Up/down for Channels 4...7
Where: O = up
1 = down
Data Format - Write Words 0 and 1
Word
Bits
Description
0 04 03 02 01 Channels 0...3
1 04 03 02 01 Channels 4...7
00000…22 mA = 0...22,000 with error steps (default)
00010…22 mA = 0…110%, with error steps
00100…22 mA = 0…104.8%, square root, with error steps