Rockwell-automation 1797-IE8NF FLEX Ex 8 Input Analog, HART and Noise Bedienungsanleitung Seite 23

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 52
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 22
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 23
Publication
1797-5.5 - September 2011
0011022 mA = 065,535, unsigned integer, with error steps
0100222 mA, with error steps
0101222 mA = -12.5112.5%, with error steps
0110422 mA = 0106%, square root, with error steps
0111420 mA = 065,535, unsigned integer, with error steps
1000Not assigned
1001Not assigned
1010Not assigned
1011022 mA = A/D count, with fixed error
11003.621 mA = NAMUR NE 43, with fixed error
1101321 mA = -6.25106.25% with fixed error
1110222 mA = -12.5112.5% with fixed error
1111Not assigned
Data Format - Write Words 2 and 3
Data
Format
Bits Format Signal Range User Range Resolution
15 14 13 12
11 10 9 8
7654
LO HI LO HI
3210
0 0000020 mA as
Milliamps
0.00 22.00 0
(0.000 mA)
22000
(22.000 mA)
0.1% of
0...20 mA
1 0001020 mA as
%
0.00 22.00 0
(0%)
11000
(110.00%)
0.2% of
0...20 mA
2 0010020 mA as
%
0.00 22.00 0
(0%)
10488
(140.88%)
0.19% of
0...20 mA
3 0011020 mA as
unsigned
integer
0.00 20.00 0
(0.000 mA)
65535
(20.000 mA)
0.03% of
0...20 mA
4 0100420 mA as
mA
2.00 22.00 2000
(2.000 mA)
22000
(22.000 mA)
0.01% of
4...20 mA
5 0101420 mA as
%
2.00 22.00 -1250
(-12.50%)
11250
(112.50%)
0.16% of
4...20 mA
Data Format - Write Words 0 and 1
Word
Bits
Description
Seitenansicht 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 51 52

Kommentare zu diesen Handbüchern

Keine Kommentare