Rockwell-automation 1756-CFM ControlLogix Configurable Flowmeter Modul Bedienungsanleitung Seite 63

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 168
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 62
63Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
Installing the Configurable Flowmeter Module 63
Power Requirements
This module receives power from the 1756 chassis power supply and requires
2 sources of power from the backplane:
300mA at 5.1V DC
16mA at 24V DC
Add this current/power value (1.7W) to the requirements of all other modules
in the chassis to prevent overloading the power supply.
ATTENTION
!
The ControlLogix system has been agency certified using
only the ControlLogix RTBs (catalog numbers
1756-TBNH and 1756-TBSH). Any application that
requires agency certification of the ControlLogix system
using other wiring termination methods may require
application specific approval by the certifying agency.
Seitenansicht 62
1 2 ... 58 59 60 61 62 63 64 65 66 67 68 ... 167 168

Kommentare zu diesen Handbüchern

Keine Kommentare