Rockwell-automation 1756-CFM ControlLogix Configurable Flowmeter Modul Bedienungsanleitung Seite 150

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 168
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 149
150Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
150 Configure Output Behavior with RSLogix 5000 Version 16 and Earlier
7. In the CFM_GenericProfileExample project, copy the following data
tags located in the Controller Tag folder.
8. In the CFM_DEMO project, paste the copied data tags into the
Controller Tags folder by using the Edit Tags tab.
9. In the CFM_GenericProfileExample project, copy ladder logic rung 1
located in the Main Routine folder.
10. In the CFM_DEMO project, paste the copied rung into the Main
Routine folder.
11. Change the Local:5 tag references to correspond to the location of your
1756-CFM module in your chassis.
12. Accept the pasted rung.
13. Delete the empty rung.
Seitenansicht 149
1 2 ... 145 146 147 148 149 150 151 152 153 154 155 ... 167 168

Kommentare zu diesen Handbüchern

Keine Kommentare