Publication 1753-PM001A-EN-P - November 2005
Connect to GuardPLC Distributed I/O Modules 2-5
The offline configuration of the module is complete. The next section
explains how to go online with the module and change the IP address
and SRS to match the offline settings.
Go Online With the Module
Make a point-to-point connection between your programming
terminal and the distributed I/O module. Over this connection,
change the IP address and SRS of the module, following these steps:
1. Right-click the module in the project tree and choose Online >
Communication Settings.
2. Enter the MAC address, which is located on the label positioned
over the RJ-45 connectors.
3. Click Get.
The IP address and SRS of the module appear. If the module is
new, it has the default IP address of 192.168.0.99, the same as
any GuardPLC controller. However, the default SRS is 60000.1.