2–14 System Component Detail
1336 FORCE — 5.9 August 1995
If you are using a PLC, you would create this same link by doing the
following:
1. Set up your block transfer read and write blocks.
2. Create your data table. For this example, your data table would
look like the following:
BTW
Data File
N10:10
0 8F04 8002 8301
0123456789
Write Link
Service
Request
Destination
Node
Source
Node
The 8002 in column 2 specifies that Node 0 of Block ID 2 (the
Set Reset FF function block) is receiving information. The 8301
specifies that Node 3 of Block ID 1 (the LIMIT function block) is
providing the information.